The building inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The building inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The building inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.
 INNINPRR
1.0 Restaurant Rear Rolled Asphalt RoofX   
1.1 Restaurant Rolled Roof FlashingsX   
1.2 Restaurant Asphalt RoofX   
1.3 Tar & Gravel RoofX   
1.4 Shingled Left Side RoofX   
1.5 Front Tarred RoofX   
1.6 Chimneys and Roof PenetrationsX   
1.7 SkylightsX   
1.8 Roof Drainage SystemsX   
1.9 Rear BalconiesX   
1.10 Roof Defects or ConditionX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
1.0 Rear roof attached to rear of Korean restaurant.
1.0 Picture 1
1.1 The rolled asphalt roof at back of Korean restaurant has multiple holes in flashing.  Recommend sealing to prevent water entry.
1.1 Picture 1
1.1 Picture 2
1.1 Picture 3
1.2
  1. Rolled asphalt roof is in good condition.
  2. Plumbing vent pipe is crooked.
  3. Roof exhaust unit shakes whole roof when operating.  Recommend installing a anti-vibration support system.
  4. Split air conditioner unit installed on roof.
  5. Front mansard type roof has exposed wood on fascia which should be maintained and painted or covered.
  6. Exposed and damaged wood fascia at soffit area of mansard roof.
1.2 Picture 1
1.2 Picture 2
1.2 Picture 3
1.2 Picture 4
1.2 Picture 5
1.2 Picture 6
1.2 Picture 7
1.3
  1. Tar and gravel roof is generally in good condition.
  2. Small gap at rear flashing is not sealed.  Recommend sealing.
  3. Patched areas at rear corner of roof.
  4. Some water pooling along left edge of roof.
  5. Skylight appears in good condition.
  6. Center shaft covered with wire to keep birds out.  Wood windows in shaft area require painting and sealing.
  7. Plumbing vent is being used to support clothes line.
1.3 Picture 1
1.3 Picture 2
1.3 Picture 3
1.3 Picture 4
1.3 Picture 5
1.3 Picture 6
1.3 Picture 7
1.4 Left side shingled roof is in good condition.
1.4 Picture 1
1.4 Picture 2
1.5
  1. There is some visible alligatoring of tar at seam area.
  2. All mortar seams have to be kept sealed to prevent water entry.
  3. Tarred seam is raised.  Recommend sealing to prevent water entry.
  4. Front brick wall flashing has many openings that require sealing.  Water will leak into apartments and commercial units if not sealed.
  5. Front wall metal flashing cap requires sealing.
  6. Rear of roof has heating cables installed in gutters and along edge of roof.  This is typically only done at ice build up areas which become a problem.
1.5 Picture 1
1.5 Picture 2
1.5 Picture 3
1.5 Picture 4
1.5 Picture 5
1.5 Picture 6
1.5 Picture 7
1.5 Picture 8
1.5 Picture 9
1.5 Picture 10
1.5 Picture 11
1.5 Picture 12
1.5 Picture 13
1.6
  1. Round chimney clay tile is broken and cracked.  Recommend repairing and installing rain cap to keep water out.
  2. Masonry chimney has missing bricks and loose mortar.  Recommend installing rain cap if still in use and sealing up if not being used.
1.6 Picture 1
1.6 Picture 2
1.6 Picture 3
1.7 Older style skylights are in good condition
1.7 Picture 1
1.7 Picture 2
1.8 Left side rear corner has split in galvanized downspout.
1.8 Picture 1
1.9 Rear apartment balconies are generally sound.  Floors have been patched and painting neglected.
1.9 Picture 1
1.10 Plumbing vent is missing extension.  Snow can block vent and prevent proper drainage.
1.10 Picture 1
The roof of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The building inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The building inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The building inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.
 INNINPRR
2.0 Wall Cladding Flashing and TrimX   
2.1 Doors (Exterior)X   
2.2 WindowsX   
2.3 Foundation Walls and Mortar JointsX   
2.4 Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable RailingsX   
2.5 Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (with respect to their effect on the condition of the building)   X
2.6 Eaves, Soffits and FasciasX   
2.7 Front of BuildingX   
2.8 Left SideX   
2.9 Interior Alley WayX   
2.10 Rear of BuildingX   
2.11 Downspout and Water EntryX   
2.12 Exterior of BuildingX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
2.1 Left side wood door in commercial area has damaged door skin.
2.1 Picture 1
2.2 Front upper window has cracks and missing concrete in sill.

Window by lane way partially obstructed, could trap water and debris and make maintenance difficult. Suggest installing window well.

2.2 Picture 1
2.2 Picture 2
2.4 All the apartment wood balconies have aged and cracked boards and paint is peeling on most railings.
2.4 Picture 1
2.5 Downspout is partially obstructed by vegetation and dumps water very close to building foundation.

Debris by back stairs to basement boiler room. Retaining wall leading to boiler room has partially subsided and settled.

2.5 Picture 1
2.5 Picture 2
2.5 Picture 3
2.7
  1. All front wood window bays have cracked and peeling paint.
  2. Right side brick joint with neighbouring building is not sealed.
2.7 Picture 1
2.7 Picture 2
2.7 Picture 3
2.8
  1. Water from Mexican restaurant air conditioner is damaging brick.  Recommend redirecting water to prevent future damage.
  2. Electrical cable running up side of exhaust vent.  Improper wiring type for exterior use and wire is not secured.
  3. Top of door canopy has peeling paint and finish.
  4. Left side bricks have been repaired under most window sills.
  5. Upper concrete window sills have cracks in concrete.
2.8 Picture 1
2.8 Picture 2
2.8 Picture 3
2.8 Picture 4
2.8 Picture 5
2.8 Picture 6
2.9
  1. Old windows missing wood trim and requiring maintenance and painting.
  2. Pile of old bricks
  3. Hot water heater exhaust penetrating basement window well.
  4. Broken glass in boarded up window.
  5. Entrance to basement and older steel fire escape.
  6. Broken glass window pane.
  7. Under apartment balcony walkway has cracks in concrete flooring.
2.9 Picture 1
2.9 Picture 2
2.9 Picture 3
2.9 Picture 4
2.9 Picture 5
2.9 Picture 6
2.9 Picture 7
2.9 Picture 8
2.10
  1. Right side upper window sill has cracked and missing concrete on sill.
  2. Left rear upper window has cracked concrete sill.
  3. Basement window is below grade. No visible drain for water.  Brick is damaged at side of window.
  4. Left side corner of rear wall has patched area of brick which are not repaired flush.  Or they may have been hit after repair.
  5. Rear addition at back of Korean restaurant has an un-finished exterior wall.
  6. Old steel fire escape from apartment balcony
2.10 Picture 1
2.10 Picture 2
2.10 Picture 3
2.10 Picture 4
2.10 Picture 5
2.10 Picture 6
2.10 Picture 7
2.10 Picture 8
2.11 Downspout secure to building.
2.11 Picture 1
The exterior of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The building inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The building inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The building inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the building inspector or other persons.
 INNINPRR
3.0 FoundationsX   
3.1 Walls (Structural)X   
3.2 Columns or PiersX   
3.3 Floors (Structural)X   
3.4 Ceilings (Structural)X   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
3.3 Basement floor joists in stores are 2 X 10 wood joists supported on masonry brick walls.
3.3 Picture 1
The structure of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
Korean Restaraunt
Eating Area
Serving Area
Kitchen Area
Cooking Area
Basement Prep Area
Basement Sitting Room
 INNINPRR
4.0 CeilingsX   
4.1 WallsX   
4.2 FloorsX   
4.3 Doors (Representative Number)X   
4.4 Windows (Representative Number)X   
4.5 Outlets and Wall SwitchesX   
4.6 Fire SuppressionX   
4.7 Life SafetyX   
4.8 Electrical DeficienciesX   
4.9 Rear AdditionX   
4.10 Basement StairsX   
4.11 Ladies WashroomX   
4.12 Mens WashroomX   
4.13 Main Electrical PanelX   
4.14 Utility RoomX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
4.2 Damaged tile at entrance to Korean restaurant.  Asphalt also has hole.  Asphalt should be city responsibility as it is their property.
4.2 Picture 1
4.5 Wall outlet in eating area has open ground.
4.5 Picture 1
4.6 Fire suppression equipment for exhaust hood.
4.6 Picture 1
4.6 Picture 2
4.7 Exit and emergency lights tested and working.
4.7 Picture 1
4.7 Picture 2
4.8
  1. Electrical cable is attached to metal stud wall across from electrical equipment.  This is not permitted as whole wall could become electrified.
  2. Open junction box in ceiling in main electrical area in basement.
  3. Open junction box and cut off electrical cable in utility room in basement.  Recommend installing cover and removing cut off cable.
  4. Improperly installed electrical cables in sitting area in basement.  Recommend having licensed electrician inspect and repair wiring.
4.8 Picture 1
4.8 Picture 2
4.8 Picture 3
4.8 Picture 4
4.9
  1. Rear addition has no heat or electrical outlets.
  2. Exhaust discharge into rear addition.  This is not permitted.
4.9 Picture 1
4.9 Picture 2
4.10 Entry to basement in Korean Restaurant.
4.10 Picture 1
4.11 Ladies washroom.
4.11 Picture 1
4.11 Picture 2
4.12 Mens washroom.
4.12 Picture 1
4.12 Picture 2
4.13
  1. Main electrical service entry panel is open.  Toronto Hydro should be notified to come and seal this cabinet as it is not supposed to be open.  400 amp service conductors exposed.
  2. Main electrical area being used for storage.  This area is supposed to be accessible at all times.
  3. Commander 200 amp panel board for restaurant.
  4. 100 amp shut off and Square D panel board for 2nd floor apartment.  Opening in panel board should be sealed with tape etc for protection.
  5. 2 Separate meters
4.13 Picture 1
4.13 Picture 2
4.13 Picture 3
4.13 Picture 4
4.13 Picture 5
4.14
  1. Natural gas furnace was not accessible for inspection due to storage in room.
  2. Heat duct in ceiling of utility room is dis-connected.
  3. Rheem rental natural gas hot water tank in utility area.  60 US gal capacity.
4.14 Picture 1
4.14 Picture 2
4.14 Picture 3
4.14 Picture 4
4.14 Picture 5
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
i'm yours
Retail Area
Storage Area
Storage sink
Basement
 INNINPRR
5.0 CeilingsX   
5.1 WallsX   
5.2 FloorsX   
5.3 Doors (Representative Number)X   
5.4 Windows (Representative Number)X   
5.5 Outlets and Wall SwitchesX   
5.6 Crawl SpaceX   
5.7 Electrical DeficienciesX   
5.8 First Floor BathroomX   
5.9 Basement BathroomX   
5.10 Hot Water TanksX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
5.0 Suspended ceiling in retail area has water stains.  No visible sign of leak.  Possible roof leak that has been repaired.
5.0 Picture 1
5.2 Trap door style entrance to basement.  Trap door has been removed.  Stairs would not meet current code requirements for safety.
5.2 Picture 1
5.5
  1. Outlet in storage area has exposed electrical cable.  Electrical cables under 1.5 m from floor are required to be protected from mechanical harm.
  2. Outlet at top of trap door stairs has reversed polarity.
5.5 Picture 1
5.5 Picture 2
5.6 Front section of basement is filled with sand like substance and separated from basement area by old wood doors.
5.6 Picture 1
5.6 Picture 2
5.7
  1. Live exposed electrical wires over GE electric hot water tank.  Wires should not be live and should also be properly terminated.
  2. No connector on wire in junction box.  Same area as live wire.
5.7 Picture 1
5.7 Picture 2
5.8 Bathroom has no sink for washing hands.
5.8 Picture 1
5.9 There is visible galvanized plumbing in basement bathroom.
5.9 Picture 1
5.9 Picture 2
5.9 Picture 3
5.10
  1. 2 Rheem natural gas rental hot water tanks -  50 US gal capacity.  Supplying 2 floor apt #1 and 3rd floor apt #2
  2. 1 GE electric hot water tank 270 liters.  Use is not identified.
5.10 Picture 1
5.10 Picture 2
5.10 Picture 3
5.10 Picture 4
5.10 Picture 5
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
St James Coffee Bar
Coffee Shop
Rear Storage
Bathroom
 INNINPRR
6.0 CeilingsX   
6.1 WallsX   
6.2 FloorsX   
6.3 Doors (Representative Number)X   
6.4 Outlets and Wall SwitchesX   
6.5 Electrical DeficienciesX   
6.6 StairsX   
6.7 PlumbingX   
6.8 Main electrical panelX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
6.1
  1. F/A pull station located at entrance.  Also ceiling mounted HAD
  2. Wall in basement bathroom is damaged by water.  Water has probably leaked down shaft from cracks in grille on sidewalk.
6.1 Picture 1
6.1 Picture 2
6.1 Picture 3
6.1 Picture 4
6.2
  1. Front entrance concrete door sill is cracked.
  2. Grille covered with concrete may lead down to basement shaft for window.
  3. Floor in basement bathroom is rotted and sagging in corner.
6.2 Picture 1
6.2 Picture 2
6.2 Picture 3
6.2 Picture 4
6.2 Picture 5
6.5 Old knob and tube wire connected to armored cable.  Wiring was not live.
6.5 Picture 1
6.6 Trap door leads to basement stairs.
6.6 Picture 1
6.6 Picture 2
6.7
  1. ABC, Galvanized pipe and cast iron drain.
  2. Insulation on pipe appears to be asbestos.  Recommend testing to ensure identify.
  3. Galvanized elbow visible at corner of basement bathroom.
  4. Toilet is loose and requires re-securing.
6.7 Picture 1
6.7 Picture 2
6.7 Picture 3
6.8 Cutler Hammer 60 amp electric panel.
6.8 Picture 1
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
Taco Restaurant
Eating Area
Kitchen
Exhaust Hood
Suppression System for Hood
Men's Bathroom
Ladies Bathroom
Food Prep Area
 INNINPRR
7.0 CeilingsX   
7.1 WallsX   
7.2 FloorsX   
7.3 Doors (Representative Number)X   
7.4 Windows (Representative Number)X   
7.5 Outlets and Wall SwitchesX   
7.6 Main Electrical PanelX   
7.7 Electrical DeficienciesX   
7.8 Hot Water TankX   
7.9 Plumbing DeficieciesX   
7.10 Air ConditioningX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
7.1 Wall has been repaired in ladies bathroom.
7.1 Picture 1
7.2 Front entrance has cracked and missing tile.
7.2 Picture 1
7.3 Door skin in mens bathroom is damaged.
7.3 Picture 1
7.6
  1. Main electrical panel is Square D 100 amp
  2. 30 amp Federal Pioneer shut off switch for kitchen appliance.
7.6 Picture 1
7.6 Picture 2
7.6 Picture 3
7.7
  1. Wall mounted electric baseboard is missing control knob and was not working at time of inspection.
  2. Switch at main panel area is missing cover plate.
  3. Electrical connection at rear ceiling is made outside of junction box.  This is not permitted.
  4. Light switch in ladies bathroom is loose and requires securing.
  5. Light switch in food prep area has been secured with tape.
7.7 Picture 1
7.7 Picture 2
7.7 Picture 3
7.7 Picture 4
7.7 Picture 5
7.8 Electric hot water tank.  No data visible due to being wrapped in energy saver blanket.
7.8 Picture 1
7.9
  1. Pipe in basement appears to be wrapped in asbestos type insulation.  Insulation would have to be tested to properly identify whether or not asbestos.
  2. Galvanized pipe hooked into cast iron pipe.
7.9 Picture 1
7.9 Picture 2
7.9 Picture 3
7.10 LG split air conditioner installed in eating area.
7.10 Picture 1
7.10 Picture 2
7.10 Picture 3
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
Seoul Fashion
Bathroom
 INNINPRR
8.0 CeilingsX   
8.1 WallsX   
8.2 FloorsX   
8.3 Doors (Representative Number)X   
8.4 Windows (Representative Number)X   
8.5 Outlets and Wall SwitchesX   
8.6 HeatingX   
8.7 Electrical DeficienciesX   
8.8 Main electrical panelX   
8.9 BathroomX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
8.0 Main floor area
8.0 Picture 1 Sewing area
8.6 Hot water rad heaters.
8.6 Picture 1
8.6 Picture 2
8.6 Picture 3
8.7
  1. Electrical cables for lights are improperly secured on ceiling.
  2. Un-protected openings on side of main panel.
8.7 Picture 1
8.7 Picture 2
8.8 Unknown type of main electrical panel.  6 - 20 amp breakers.
8.8 Picture 1
8.9 Bathroom has no exhaust fan or electrical outlet.
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
The building inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The building inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The building inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The building inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.
 INNINPRR
9.0 Plumbing Drain, Waste and Vent SystemsX   
9.1 Plumbing Water Supply and Distribution Systems and FixturesX   
9.2 Hot Water Systems, Controls, Chimneys, Flues and VentsX   
9.3 Fuel Storage and Distribution Systems (interior fuel storage, piping, venting, supports, leaks)X   
9.4 Sprinkler System  X 
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
9.0 Copper, Galvanized, ABS and Cast Iron drains
9.1 Majority of water supply is copper although there was some galvanized piping located in Commercial area basements.
9.2 Hot water tanks are majority rental and are located though out complex.
The plumbing in the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant building waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
Kitchen
Eating Area
Bathroom
Living Room
 INNINPRR
10.0 WINDOW DEFECTS   X
10.1 LIVING ROOMX   
10.2 BATHROOMX   
10.3 KITCHENX   
10.4 BEDROOM 1X   
10.5 BEDROOM 2X   
10.6 ELECTRICAL DEFECTSX   
10.7 MAIN ELECTRICAL PANELX   
10.8 STAIRSX   
10.9 SMOKE DETECTORX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
10.0 All windows have weather damage but are operable. Sanding, priming and painting required.
10.0 Picture 1
10.1 Wood window sill is weathered and requires maintenance and painting.
10.1 Picture 1
10.1 Picture 2
10.2 No exhaust fan installed in bathroom.
10.2 Picture 1
10.2 Picture 2
10.6 No power to bedroom wall outlet.
10.7
  1. Siemens 100 amp main electrical panel.
  2. Main electrical meters and panel boards at base of stairs at street level.
10.7 Picture 1
10.7 Picture 2
10.7 Picture 3
10.8 Steel fire escape
10.8 Picture 1
10.9 Kiddie smoke detector, typical installation in all stairwells and apartments.
10.9 Picture 1
Top Table of Contents Bottom
Apt # 2 Eating Area
Bathroom
Bedroom
Bedroom
 INNINPRR
11.0 CEILING DEFECTSX   
11.1 WALL DEFECTSX   
11.2 WINDOW DEFECTS   X
11.3 LIVING ROOMX   
11.4 BATHROOMX   
11.5 BEDROOM 1X   
11.6 BEDROOM 2X   
11.7 ELECTRICAL DEFECTSX   
11.8 STAIRSX   
11.9 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
11.0 Some past water damage to bathroom ceiling. Skylight show no sign of leaking now and the walls and ceiling are dry. Ceiling needs to be sanded, primed and painted in the washroom.
11.0 Picture 1
11.0 Picture 2
11.1 Some small patches of cracked or bubbling paint in living room.
11.1 Picture 1
11.2 All windows have weather damage but are operable. Sanding, priming and painting required. 
11.2 Picture 1
11.3 Some past water damage to bathroom ceiling. Skylight show no sign of leaking now and the walls and ceiling are dry. Ceiling needs to be sanded, primed and painted in the washroom.
11.3 Picture 1
11.7 Bedroom outlet is missing cover.  Recommend installing electrical cover.
11.7 Picture 1
11.8 Unit 363 hallway has bubbling paint on hallway.
11.8 Picture 1
11.9 100 amp Siemens electrical panel.
11.9 Picture 1
Top Table of Contents Bottom
Bedroom
End Bedroom
Bathroom
Kitchen
 INNINPRR
12.0 WALL DEFECTS   X
12.1 WINDOW DEFECTS   X
12.2 BATHROOMX   
12.3 KITCHENX   
12.4 BEDROOM 1X   
12.5 BEDROOM 2X   
12.6 ELECTRICAL DEFECTS   X
12.7 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
12.0 Bubbling paint on stairwell wall is sign of prior water damage, currently dry.
12.0 Picture 1
12.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
12.2 Electrical box at floor area.
12.2 Picture 1
12.4 Un-used fireplace in unit.  Ensure tenants do not try and use.
12.4 Picture 1
12.6 No GFCI in kitchen or washroom. Recent electrical renovation requires upgrading to meet code.
12.7 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
Living Area
Kitchen
 INNINPRR
13.0 CEILING DEFECTS   X
13.1 WALL DEFECTS   X
13.2 WINDOW DEFECTS   X
13.3 LIVING ROOMX   
13.4 BATHROOM   X
13.5 KITCHENX   
13.6 BEDROOM 1X   
13.7 BEDROOM 2X   
13.8 ELECTRICAL DEFECTSX   
13.9 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
13.0 Section of plaster ceiling has been patched with drywall. The patch is 1/2" lower than the plaster.
13.0 Picture 1
13.1 Peeling paint and plaster in washroom.
13.2 All windows have weather damage but are operable. Sanding, priming and painting required. 
13.2 Picture 1
13.4 Bathroom has peeling paint on wall and ceiling, hot neutral outlet, and loose toilet.
13.4 Picture 1
13.4 Picture 2
13.4 Picture 3
13.6 Bedroom has ceiling defect. Otherwise bedroom is in good condition.
13.6 Picture 1
13.7 Bedroom in good condition.
13.8
  1. Broken switch in Bedroom 2.
  2. Hot neutral on washroom outlet.
  3. No GFCI in kitchen. Recent electrical renovation requires upgrading to meet code.
13.8 Picture 1
13.9 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
Living Room
 INNINPRR
14.0 FLOOR DEFECTS   X
14.1 WINDOW DEFECTS   X
14.2 LIVING ROOMX   
14.3 BATHROOMX   
14.4 KITCHENX   
14.5 KITCHEN FIXTURES AND APPLIANCESX   
14.6 BEDROOM 1X   
14.7 BEDROOM 2X   
14.8 ELECTRICAL DEFECTS   X
14.9 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
14.0 Bedroom door rubs on floor and has left scratch marks on the floor.
14.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
14.4 Kitchen in good condition. See electrical defects.
14.4 Picture 1
14.4 Picture 2
14.4 Picture 3
14.4 Picture 4
14.6 Bedroom in good condition.
14.6 Picture 1
14.7 Bedroom in good condition. See floor defects.
14.7 Picture 1
14.7 Picture 2
14.8
  1. Open ground outlets in kitchen by counter and by fridge.
  2. 2 prong outlet by toilet (ungrounded).

14.9 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
 INNINPRR
15.0 WALL DEFECTS   X
15.1 WINDOW DEFECTS   X
15.2 LIVING ROOMX   
15.3 BATHROOMX   
15.4 BATHROOM FIXTURESX   
15.5 KITCHENX   
15.6 KITCHEN FIXTURES AND APPLIANCESX   
15.7 BEDROOM 1X   
15.8 BEDROOM 2X   
15.9 ELECTRICAL DEFECTS   X
15.10 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
15.0 Some peeling paint in washroom.
15.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
15.1 Picture 1
15.3 Some peeling paint.
15.3 Picture 1
15.5 Kitchen in good condition. See electrical defect. 
15.5 Picture 1
15.7 Bedroom in good condition.
15.7 Picture 1
15.7 Picture 2
15.9
  1. Open ground in kitchen.
  2. 2 prong outlet in washroom (ungrounded).

15.10 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
Eating Area
 INNINPRR
16.0 WALL DEFECTS   X
16.1 WINDOW DEFECTS   X
16.2 LIVING ROOMX   
16.3 BATHROOMX   
16.4 KITCHENX   
16.5 BEDROOM 1   X
16.6 BEDROOM 2X   
16.7 PLUMBING DEFECTSX   
16.8 ELECTRICAL DEFECTS   X
16.9 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
16.0 Few cracked bricks beside basement exterior door.
16.0 Picture 1
16.1 Cracked window pane at back of apartment. All windows have weather damage but are operable. Sanding, priming and painting required.
16.1 Picture 1
16.3 Bathroom in good condition. See plumbing defects.
16.3 Picture 1
16.5 Bedroom in good condition. See electrical defect.
16.6 Bedroom in good condition. Fireplace located in this room.
16.6 Picture 1
16.7 Tub shower diverter valve leaks when filling bath with spigot.
16.7 Picture 1
16.8 Broken outlet cover in bedroom.
16.8 Picture 1
16.9 Electrical panel is 100 amp Eaton / Cutler-Hammer 
16.9 Picture 1
Top Table of Contents Bottom
 INNINPRR
17.0 WALL DEFECTS   X
17.1 WINDOW DEFECTS   X
17.2 LIVING ROOMX   
17.3 BATHROOMX   
17.4 KITCHENX   
17.5 KITCHEN FIXTURES AND APPLIANCESX   
17.6 BEDROOM 1X   
17.7 BEDROOM 2X   
17.8 MAIN ELECTRICAL PANELX   
17.9 STAIRSX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
17.0 Cracked and missing parging by exterior door.
17.0 Picture 1
17.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
17.2 Room in good condition.
17.2 Picture 1
17.4 Kitchen in good condition.
17.8 Electrical panel is 100 amp Eaton / Cutler-Hammer 
17.8 Picture 1
17.9 Porch railing 30 1/2" in height.
Top Table of Contents Bottom
 INNINPRR
18.0 CEILING DEFECTS   X
18.1 FLOOR DEFECTS   X
18.2 WINDOW DEFECTS   X
18.3 LIVING ROOMX   
18.4 BATHROOMX   
18.5 KITCHEN   X
18.6 KITCHEN FIXTURES AND APPLIANCESX   
18.7 BEDROOM 1X   
18.8 BEDROOM 2X   
18.9 ELECTRICAL DEFECTS   X
18.10 MAIN ELECTRICAL PANELX   
18.11 STAIRS & RAILINGS   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
18.0 Peeling paint on bedroom ceiling.
18.1
  1. Kitchen floor in very poor condition. Some loose floor boards.
  2. Living Room floors in poor condition. 80% finish worn off.
  3. Washroom and Bedroom floors in poor condition. 50% finish worn off.
18.1 Picture 1
18.2 All windows have weather damage but are operable. Sanding, priming and painting required. 
18.3 Room in fair condition. See floor defects.
18.3 Picture 1
18.4 Washroom in fair condition. See floor defects.
18.4 Picture 1
18.4 Picture 2
18.5 Kitchen in poor condition. Some cupboard doors missing. See floor defects.
18.9 Loose outlet in bedroom.
18.9 Picture 1
18.10 Electrical panel is 100 amp Eaton / Cutler-Hammer 
18.10 Picture 1
18.11 Balcony railing 30 1/2" high and not secure.
18.11 Picture 1
Top Table of Contents Bottom
 INNINPRR
19.0 PLUMBINGX   
19.1 ELECTRICALX   
19.2 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
19.0 All hot water tanks by GSW, 182 litre capacity, Serial Numbers: U0926F701317, U0924F705998, U0921F700725, U0926F701348, U0926F701342, U0845F708913, U0845F708896, U0803F705364, U0918F702780.
19.0 Picture 1
19.0 Picture 2
19.0 Picture 3
19.0 Picture 4
19.0 Picture 5
19.1 Electrical wires in basement
19.1 Picture 1
19.2 Main electrical meters for units.
19.2 Picture 1
19.2 Picture 2
Top Table of Contents Bottom
 INNINPRR
20.0 FLOOR DEFECTS   X
20.1 WINDOW DEFECTS   X
20.2 LIVING ROOMX   
20.3 BATHROOM   X
20.4 KITCHENX   
20.5 KITCHEN FIXTURES AND APPLIANCESX   
20.6 BEDROOM 1X   
20.7 BEDROOM 2X   
20.8 MAIN ELECTRICAL PANELX   
20.9 STAIRS & RAILINGS   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
20.0 Front porch paint peeling.
20.0 Picture 1
20.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
20.2 Room in good condition.
20.2 Picture 1
20.3 Bathroom in fair condition. Toilet loose.
20.3 Picture 1
20.8 Electrical panel is 100 amp Eaton / Cutler-Hammer 
20.8 Picture 1
20.9 Balcony railing 30" height, loose.
20.9 Picture 1
Top Table of Contents Bottom
 INNINPRR
21.0 WALL DEFECTS   X
21.1 WINDOW DEFECTS   X
21.2 LIVING ROOMX   
21.3 BATHROOMX   
21.4 BATHROOM FIXTURESX   
21.5 KITCHENX   
21.6 KITCHEN FIXTURES AND APPLIANCESX   
21.7 BEDROOM 1X   
21.8 BEDROOM 2X   
21.9 MAIN ELECTRICAL PANELX   
21.10 STAIRS & RAILINGS   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
21.0 Moisture damage to drywall
21.0 Picture 1
21.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
21.3 Bathroom in fair condition. See wall defects.
21.9 Electrical panel is 100 amp Eaton / Cutler-Hammer 
21.10 Railings on balcony
21.10 Picture 1
21.10 Picture 2
Top Table of Contents Bottom
 INNINPRR
22.0 LIVING ROOMX   
22.1 BATHROOMX   
22.2 KITCHENX   
22.3 KITCHEN FIXTURES AND APPLIANCESX   
22.4 BEDROOM 1X   
22.5 BEDROOM 2X   
22.6 ELECTRICAL DEFECTS   X
22.7 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
22.4 Bedroom in good condition. See electrical defects.
22.6
  1. Some older outlets present.
  2. Old outlet in bedroom is missing cover.
22.6 Picture 1
22.7 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
 INNINPRR
23.0 WINDOW DEFECTS   X
23.1 LIVING ROOMX   
23.2 BATHROOMX   
23.3 KITCHENX   
23.4 KITCHEN FIXTURES AND APPLIANCESX   
23.5 BEDROOM 1X   
23.6 BEDROOM 2X   
23.7 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
23.0 All windows have weather damage but are operable. Sanding, priming and painting required. 
23.1 Room in good condition.
23.1 Picture 1
23.5 Bedroom in good condition.
23.5 Picture 1
23.7 Electrical panel is 100 amp Eaton / Cutler-Hammer 
Top Table of Contents Bottom
 INNINPRR
24.0 CEILING DEFECTS   X
24.1 WINDOW DEFECTS   X
24.2 LIVING ROOMX   
24.3 BATHROOMX   
24.4 KITCHENX   
24.5 KITCHEN FIXTURES AND APPLIANCESX   
24.6 BEDROOM 1X   
24.7 BEDROOM 2X   
24.8 MAIN ELECTRICAL PANELX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
24.0 Some peeling paint on washroom ceiling. Ceiling is a painted panel type.
24.0 Picture 1
24.1 All windows have weather damage but are operable. Sanding, priming and painting required. 
24.1 Picture 1
24.3 Bathroom in fair condition. See ceiling defects.
24.8 Electrical panel is 100 amp Eaton / Cutler-Hammer.
Top Table of Contents Bottom
 INNINPRR
25.0.A OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.A There are basically four main roofs with various products used.
  1. Rolled asphalt roofing has been used on rear roof and some smaller roof additions.
  2. Tar and gravel roof used on Clinton street rear of apartments.
  3. Shingled roof at front of Clinton street apartments.
  4. Front Street commercial roofs are rolled asphalt roofing with hot mopped tar.  Core sample would have to be taken to determine if this was original or repaired with hot tar.

Overall Condition of Roof

  1. The roof flashings on rear asphalt rolled roof and hot mopped tar have a significant amount of gaps and cracks which will allow water entry into building.
  2. The metal wall flashing at edge of roof requires to be secured and sealed.
  3. Any brick which is exposed vertically will have to be monitored and masonry joints repaired as required.
  4. Asphalt and tar has been used to protect tops of parapet walls and will also have to be monitored to ensure cracks and gaps are sealed.
  5. Chimney's that are in use should have rain caps etc installed to prevent water from entering. Cap and seal any un-used chimney's.

Top Table of Contents Bottom
 INNINPRR
25.0.B OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.B
  1. Building is two stories in height with brick veneer covering exterior of building.
  2. Bricks under Side street apartment windows have been repaired.  This is common for bricks to spall from water entry from cracks and gaps in window sills.  Preventive maintenance in this area will save the expense of replacing bricks in future. Ensure all window sills are caulked and any loose mortar is removed and repaired.  Water will damage brick if allowed to attack from a vertical entry point.
  3. Recommend sealing grate at Coffee Shop sidewalk as it seems to have been an entry point for water in past and probably will again.
  4. Rear wood balconies should be better maintained and painted.
  5. Seal any large cracks in concrete to prevent water entry and expansion due to freezing. This is particularly noticeable in walkway under balconies of apartments.
  6. Rear addition to Front Street restaurant is poorly constructed with exterior finish not being completed.
  7. Front wood trim on bay windows on Front Street apartments requires maintenance and painting.
  8. Left side of Mexican restaurant has A/C water dripping on brick which will eventually cause significant damage.
  9. Left side exterior wood door finish is deteriorating and eventually door will require replacement.
  10. There are a number of wood windows in very poor condition.  The enclosed shaft has windows that require maintenance and painting.  Also the alleyway has windows with missing sections, cracked glass and also require maintenance and painting.

Top Table of Contents Bottom
 INNINPRR
25.0.C OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.C
  1. Some of the Commercial property bathrooms were constructed adhoc by tenants and do not meet any of today's code requirements.  There is one unit with only a toilet and no sink to wash hands after using toilet.
  2. There is some areas of galvanized piping visible in commercial units.  Typically in basements.
  3. There is some probable asbestos pipe insulation in a couple of the Commercial Units.  This would have to be tested to determine if asbestos was present.
  4. There is a older cast iron still in use in building.  Most of water supply is copper pipe.

Top Table of Contents Bottom
 INNINPRR
25.0.D OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.D
  1. Most of visible electrical problems are due to modifications made by tenants.  The typical deficiencies found are missing electrical cover plates,  loose boxes and fittings, poorly connected electrical cables and un-secured and un-protected electrical cables.
  2. There are a number of un-used electrical wires through out commercial buildings that should be removed.  These are mainly found in the basement area.
  3. The 400 amp service panel in basement of Korean restaurant is open.  This panel is typically sealed by Toronto Hydro and should not be open.

Top Table of Contents Bottom
 INNINPRR
25.0.E OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.E Weil-McLain boiler in basement supplies hot water to radiators in all apartments.  Unit was not in operation at time of inspection,
25.0.E Picture 1
25.0.E Picture 2
25.0.E Picture 3
25.0.E Picture 4
25.0.E Picture 5
Top Table of Contents Bottom
 INNINPRR
25.0.F OverviewX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
 
Comments:
25.0.F
  1. Two storey building with brick veneer exterior built on masonry brick and concrete foundation.
  2. Floor support is provided by 2 X 10 wood joists supported on brick masonry walls.
  3. Steel fire escapes are older but all appear in good condition.
     

Fire Separations

  1. Typically in Commercial Buildings there is a required fire separation between a basement, main floor and any units above.  Most of the units inspected have holes in the existing fire separation between basement and main floor.  Usually these penetrations are made for plumbing, electrical or heating access or modification.
  2. Depending on the knowledge and diligence of the fire inspectors, you could be required to repair any required fire separation between basements and main floors.


Prepared Using HomeGauge
http://www.HomeGauge.com : Licensed To Napoleon Home Inspections Inc.
Top Table of Contents Bottom
 

General Summary


Napoleon Home Inspections

7 Stollar Blvd
Barrie, ON
L4M 6N8

Email roger@napoleon.cc
Phone 705-795-8255
Toll Free 888-818-8608

Customer
John Green

Address
1250 Main Street
Paper Town
Agloe NY

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing, Roof Structure & Chimneys
1.1   Restaurant Rolled Roof Flashings  
  Inspected  
The rolled asphalt roof at back of Korean restaurant has multiple holes in flashing.  Recommend sealing to prevent water entry.
1.2   Restaurant Asphalt Roof  
  Inspected  
  1. Rolled asphalt roof is in good condition.
  2. Plumbing vent pipe is crooked.
  3. Roof exhaust unit shakes whole roof when operating.  Recommend installing a anti-vibration support system.
  4. Split air conditioner unit installed on roof.
  5. Front mansard type roof has exposed wood on fascia which should be maintained and painted or covered.
  6. Exposed and damaged wood fascia at soffit area of mansard roof.
1.3   Tar & Gravel Roof  
  Inspected  
  1. Tar and gravel roof is generally in good condition.
  2. Small gap at rear flashing is not sealed.  Recommend sealing.
  3. Patched areas at rear corner of roof.
  4. Some water pooling along left edge of roof.
  5. Skylight appears in good condition.
  6. Center shaft covered with wire to keep birds out.  Wood windows in shaft area require painting and sealing.
  7. Plumbing vent is being used to support clothes line.
1.5   Front Tarred Roof  
  Inspected  
  1. There is some visible alligatoring of tar at seam area.
  2. All mortar seams have to be kept sealed to prevent water entry.
  3. Tarred seam is raised.  Recommend sealing to prevent water entry.
  4. Front brick wall flashing has many openings that require sealing.  Water will leak into apartments and commercial units if not sealed.
  5. Front wall metal flashing cap requires sealing.
  6. Rear of roof has heating cables installed in gutters and along edge of roof.  This is typically only done at ice build up areas which become a problem.
1.6   Chimneys and Roof Penetrations  
  Inspected  
  1. Round chimney clay tile is broken and cracked.  Recommend repairing and installing rain cap to keep water out.
  2. Masonry chimney has missing bricks and loose mortar.  Recommend installing rain cap if still in use and sealing up if not being used.
1.8   Roof Drainage Systems  
  Inspected  
Left side rear corner has split in galvanized downspout.
1.9   Rear Balconies  
  Inspected  
Rear apartment balconies are generally sound.  Floors have been patched and painting neglected.

2.  Exterior
2.2   Windows  
  Inspected  
Front upper window has cracks and missing concrete in sill.

Window by lane way partially obstructed, could trap water and debris and make maintenance difficult. Suggest installing window well.

2.4   Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings  
  Inspected  
All the apartment wood balconies have aged and cracked boards and paint is peeling on most railings.
2.7   Front of Building  
  Inspected  
  1. All front wood window bays have cracked and peeling paint.
  2. Right side brick joint with neighbouring building is not sealed.
2.8   Left Side  
  Inspected  
  1. Water from Mexican restaurant air conditioner is damaging brick.  Recommend redirecting water to prevent future damage.
  2. Electrical cable running up side of exhaust vent.  Improper wiring type for exterior use and wire is not secured.
  3. Top of door canopy has peeling paint and finish.
  4. Left side bricks have been repaired under most window sills.
  5. Upper concrete window sills have cracks in concrete.
2.9   Interior Alley Way  
  Inspected  
  1. Old windows missing wood trim and requiring maintenance and painting.
  2. Pile of old bricks
  3. Hot water heater exhaust penetrating basement window well.
  4. Broken glass in boarded up window.
  5. Entrance to basement and older steel fire escape.
  6. Broken glass window pane.
  7. Under apartment balcony walkway has cracks in concrete flooring.
2.10   Rear of Building  
  Inspected  
  1. Right side upper window sill has cracked and missing concrete on sill.
  2. Left rear upper window has cracked concrete sill.
  3. Basement window is below grade. No visible drain for water.  Brick is damaged at side of window.
  4. Left side corner of rear wall has patched area of brick which are not repaired flush.  Or they may have been hit after repair.
  5. Rear addition at back of Korean restaurant has an un-finished exterior wall.
  6. Old steel fire escape from apartment balcony

4.  Restaurant
4.2   Floors  
  Inspected  
Damaged tile at entrance to Korean restaurant.  Asphalt also has hole.  Asphalt should be city responsibility as it is their property.

5.  Novelty Store
5.0   Ceilings  
  Inspected  
Suspended ceiling in retail area has water stains.  No visible sign of leak.  Possible roof leak that has been repaired.

6.   Coffee Bar
6.1   Walls  
  Inspected  
  1. F/A pull station located at entrance.  Also ceiling mounted HAD
  2. Wall in basement bathroom is damaged by water.  Water has probably leaked down shaft from cracks in grille on sidewalk.

7.  Mexican Food
7.2   Floors  
  Inspected  
Front entrance has cracked and missing tile.
7.3   Doors (Representative Number)  
  Inspected  
Door skin in mens bathroom is damaged.

10.  Front Apt #1
10.1   LIVING ROOM  
  Inspected  
Wood window sill is weathered and requires maintenance and painting.
10.2   BATHROOM  
  Inspected  
No exhaust fan installed in bathroom.

11.  Front Apt #2
11.8   STAIRS  
  Inspected  
Unit 363 hallway has bubbling paint on hallway.

12.  Side Street Apt #1
12.4   BEDROOM 1  
  Inspected  
Un-used fireplace in unit.  Ensure tenants do not try and use.

13.  Side Street Apt #2
13.0   CEILING DEFECTS  
  Repair or Replace  
Section of plaster ceiling has been patched with drywall. The patch is 1/2" lower than the plaster.
13.1   WALL DEFECTS  
  Repair or Replace  
Peeling paint and plaster in washroom.
13.2   WINDOW DEFECTS  
  Repair or Replace  
All windows have weather damage but are operable. Sanding, priming and painting required. 
13.4   BATHROOM  
  Repair or Replace  
Bathroom has peeling paint on wall and ceiling, hot neutral outlet, and loose toilet.
13.6   BEDROOM 1  
  Inspected  
Bedroom has ceiling defect. Otherwise bedroom is in good condition.

14.  Side Street Apt #3
14.0   FLOOR DEFECTS  
  Repair or Replace  
Bedroom door rubs on floor and has left scratch marks on the floor.
14.1   WINDOW DEFECTS  
  Repair or Replace  
All windows have weather damage but are operable. Sanding, priming and painting required. 

15.  Side Street Apt #4
15.0   WALL DEFECTS  
  Repair or Replace  
Some peeling paint in washroom.
15.1   WINDOW DEFECTS  
  Repair or Replace  
All windows have weather damage but are operable. Sanding, priming and painting required. 
15.3   BATHROOM  
  Inspected  
Some peeling paint.

16.  Side Street Basement Apt
16.0   WALL DEFECTS  
  Repair or Replace  
Few cracked bricks beside basement exterior door.
16.1   WINDOW DEFECTS  
  Repair or Replace  
Cracked window pane at back of apartment. All windows have weather damage but are operable. Sanding, priming and painting required.

17.  Side Avenue Apt #1
17.0   WALL DEFECTS  
  Repair or Replace  
Cracked and missing parging by exterior door.
17.1   WINDOW DEFECTS  
  Repair or Replace  
All windows have weather damage but are operable. Sanding, priming and painting required. 


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Napoleon Home Inspections Inc.
Top Table of Contents Bottom
 

Electrical Summary


Napoleon Home Inspections

7 Stollar Blvd
Barrie, ON
L4M 6N8

Email roger@napoleon.cc
Phone 705-795-8255
Toll Free 888-818-8608

Customer
John Green

Address
1250 Main Street
Paper Town
Agloe NY

The following Electrical items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

4.  Restaurant
4.5   Outlets and Wall Switches  
  Inspected  
Wall outlet in eating area has open ground.
4.8   Electrical Deficiencies  
  Inspected  
  1. Electrical cable is attached to metal stud wall across from electrical equipment.  This is not permitted as whole wall could become electrified.
  2. Open junction box in ceiling in main electrical area in basement.
  3. Open junction box and cut off electrical cable in utility room in basement.  Recommend installing cover and removing cut off cable.
  4. Improperly installed electrical cables in sitting area in basement.  Recommend having licensed electrician inspect and repair wiring.

5.  Novelty Store
5.5   Outlets and Wall Switches  
  Inspected  
  1. Outlet in storage area has exposed electrical cable.  Electrical cables under 1.5 m from floor are required to be protected from mechanical harm.
  2. Outlet at top of trap door stairs has reversed polarity.

7.  Mexican Food
7.7   Electrical Deficiencies  
  Inspected  
  1. Wall mounted electric baseboard is missing control knob and was not working at time of inspection.
  2. Switch at main panel area is missing cover plate.
  3. Electrical connection at rear ceiling is made outside of junction box.  This is not permitted.
  4. Light switch in ladies bathroom is loose and requires securing.
  5. Light switch in food prep area has been secured with tape.

8.  Fashion Store
8.7   Electrical Deficiencies  
  Inspected  
  1. Electrical cables for lights are improperly secured on ceiling.
  2. Un-protected openings on side of main panel.

10.  Front Apt #1
10.6   ELECTRICAL DEFECTS  
  Inspected  
No power to bedroom wall outlet.

11.  Front Apt #2
11.7   ELECTRICAL DEFECTS  
  Inspected  
Bedroom outlet is missing cover.  Recommend installing electrical cover.

12.  Side Street Apt #1
12.6   ELECTRICAL DEFECTS  
  Repair or Replace  
No GFCI in kitchen or washroom. Recent electrical renovation requires upgrading to meet code.

13.  Side Street Apt #2
13.7   BEDROOM 2  
  Inspected  
Bedroom in good condition.
13.8   ELECTRICAL DEFECTS  
  Inspected  
  1. Broken switch in Bedroom 2.
  2. Hot neutral on washroom outlet.
  3. No GFCI in kitchen. Recent electrical renovation requires upgrading to meet code.

14.  Side Street Apt #3
14.8   ELECTRICAL DEFECTS  
  Repair or Replace  
  1. Open ground outlets in kitchen by counter and by fridge.
  2. 2 prong outlet by toilet (ungrounded).

15.  Side Street Apt #4
15.9   ELECTRICAL DEFECTS  
  Repair or Replace  
  1. Open ground in kitchen.
  2. 2 prong outlet in washroom (ungrounded).

16.  Side Street Basement Apt
16.8   ELECTRICAL DEFECTS  
  Repair or Replace  
Broken outlet cover in bedroom.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Napoleon Home Inspections Inc.
Top Table of Contents Bottom
 

Plumbing Summary


Napoleon Home Inspections

7 Stollar Blvd
Barrie, ON
L4M 6N8

Email roger@napoleon.cc
Phone 705-795-8255
Toll Free 888-818-8608

Customer
John Green

Address
1250 Main Street
Paper Town
Agloe NY

The following Plumbing items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing, Roof Structure & Chimneys
1.10   Roof Defects or Condition  
  Inspected  
Plumbing vent is missing extension.  Snow can block vent and prevent proper drainage.

5.  Novelty Store
5.8   First Floor Bathroom  
  Inspected  
Bathroom has no sink for washing hands.
5.9   Basement Bathroom  
  Inspected  
There is visible galvanized plumbing in basement bathroom.

6.   Coffee Bar
6.7   Plumbing  
  Inspected  
  1. ABC, Galvanized pipe and cast iron drain.
  2. Insulation on pipe appears to be asbestos.  Recommend testing to ensure identify.
  3. Galvanized elbow visible at corner of basement bathroom.
  4. Toilet is loose and requires re-securing.

7.  Mexican Food
7.9   Plumbing Deficiecies  
  Inspected  
  1. Pipe in basement appears to be wrapped in asbestos type insulation.  Insulation would have to be tested to properly identify whether or not asbestos.
  2. Galvanized pipe hooked into cast iron pipe.

13.  Side Street Apt #2
13.4   BATHROOM  
  Repair or Replace  
Bathroom has peeling paint on wall and ceiling, hot neutral outlet, and loose toilet.

16.  Side Street Basement Apt
16.7   PLUMBING DEFECTS  
  Inspected  
Tub shower diverter valve leaks when filling bath with spigot.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Napoleon Home Inspections Inc.
Top Table of Contents Bottom
 

Heating Cooling / Summary


Napoleon Home Inspections

7 Stollar Blvd
Barrie, ON
L4M 6N8

Email roger@napoleon.cc
Phone 705-795-8255
Toll Free 888-818-8608

Customer
John Green

Address
1250 Main Street
Paper Town
Agloe NY

The following Heating and Cooling items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

2.  Exterior
2.8   Left Side  
  Inspected  
  1. Water from Mexican restaurant air conditioner is damaging brick.  Recommend redirecting water to prevent future damage.
  2. Electrical cable running up side of exhaust vent.  Improper wiring type for exterior use and wire is not secured.
  3. Top of door canopy has peeling paint and finish.
  4. Left side bricks have been repaired under most window sills.
  5. Upper concrete window sills have cracks in concrete.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Napoleon Home Inspections Inc.
Top Table of Contents Bottom
 
  INVOICE

Napoleon Home Inspections
7 Stollar Blvd
Barrie, ON
L4M 6N8

Email roger@napoleon.cc
Phone 705-795-8255
Toll Free 888-818-8608
Inspected By:  Roger Frost - Certified Building Code Official
Inspection Date: 8/31/2011
Report ID: 110831

Customer Info: Inspection Property:
John Green


Customer's Real Estate Professional:

 
1250 Main Street
Paper Town
Agloe NY
 

Inspection Fee:

ServicePriceAmountSub-Total
Commercial Inspection 3700.00 1 3700.00

Tax $0.00
Total Price $3700.00

Payment Method: Invoice Included with Report
Payment Status: Invoice Sent
Note: Checks In The Mail

Top Table of Contents Bottom
 

Inspection Agreement

This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon prior to the preparation of this report and a signed copy of the agreement is available upon request. An unsigned copy of the agreement may be attached to this report for your information or it may also be available on the company web site.